Fujitsu Check-run Unfinished Error
print icon
Check-run Unfinished Error
 
Check-run unfinished error codes by model type: Typically will be on the AOU45RLXFZ Fujitsu Outdoor Unit
 
1x Operation & 5x Timer flash:
 
ASU7RLF1, ASU7RLF, ASU9RLF1, ASU9RLF, ASU12RLF1, ASU12RLF, ASU18RLF, ASU15RLS, ASU15RLS2, ASU15RLF1, ASU24RLF, ARU7RLF, ARU9RLF, ARU12RLF, ARU18RLF, ARU24RLF, AUU7RLF, AUU9RLF, AUU12RLF, AUU18RLF, AGU9RLF, AGU12RLF & AGU15RLF
 
 
 
 E156:
 
AOU48RLXFZ & AOU48RLXFZ1
 
 
 
15  Wired remote: 
 
UTY-RNNUM, UTY-RVNUM, UTY-RSNUM & UTY-DMMUM
 
 
 
 Check-run Unfinished Error Troubleshooting Checklist
 
  1. Begin by going to each indoor unit and powering them down with the remote or wired remotes first. 
  2. Once all indoor units have been powered down by remote proceed to then remove power to the outdoor disconnect for at least 5 minutes. Also, turn off power to the branch boxes and turn them back on within 1 minute of each other.
  3. After 5 minutes, turn the power back on to the disconnect.
  4. Initialize the Check-run procedure once again and normal operation should resume. For instructions on how to initialize the Check-run see attached Check-run Procedure. Make sure no indoor units are turned on or settings changed during the Check-run process as this will undo the Check-run and would need to be started from the beginning again.