Fujitsu 94 Error (Over Current Trip)
print icon
Over Current (Trip detection) Error
 
Over current error codes by model:
 
9x Operation & 4x Timer:
 
RL2 series, RLS3 series, RLS2 series, RLB/RLXB series, RLF series, RLF1 series, LUAS1 series, LMAS series, LZBS series, LZAS series, LPAS series, RGLX series, RLE series
 
 
 
5x Operation & 3x Timer:
 
RLS series, RLXS series, CQ series, RQ series, R2 series, RL series, RML series, RMLQ series, CLX series, CLX1 series, RLX series, RLXQ series, CL1 series, CL series, RLQ series
 
 
 
2 flashes on Power Mode LED, Solid Error LED, 9 flashes on L1, 4 flashes on L2, solid L6 LED:
 
AOU30RLXEH
 
 
 
9 flashes on LED A, 4 flashes on LED B & solid LED F:
 
 AOU36RLXFZH & AOU45RLXFZ
 
 
 
Continuous Operation flash & 11x Timer flash:
 
ABU18RULX, ABU24RULX & ABU36RSLX
 
 
 
E941:
 
AOU48RLXFZ & AOU48RLXFZ1
 
 
 
51 / 12 Wired remote: 
 
UTY-RNBYU, UTY-RNNUM, UTY-RVNUM, UTY-RSNUM, & UTY-RNRUZ series, UTY-RSRY, UTY-RHRY
 
 
 
Over Current Error (CT Error) Troubleshooting Checklist
 
  1. Check for clogged fins on the heat exchanger and/or obstructions in the air passages.
  2. If no obstructions are found proceed to ohm the condenser fan motor. The compressor should also be ohmed out as well. 
  3. If fan motor ohms within proper readings replace the Main Control board.
  4. If the Main Control board has already been replaced then replace the compressor, Main Control board, IPM and ACTPM boards.
  5. Also, verify line sets!