Fujitsu 97 Error (Outdoor Fan Motor Error)
print icon
 

General Fan Motor Check Steps

  1. Check DC Voltage

    • Use caution when checking DC volts on fan motors.

  2. Check Fuse

    • Inspect the 3.15A fuse on the control board using a continuity test.

    • If the fuse is open, replace the control board and fan motor.

  3. Spin Test

    • Unplug the fan motor from the control board.

    • Manually spin the fan blade; it should rotate freely for two full revolutions.

  4. Ohm Test

    • Use a meter with a 400k ohm rating or higher.

    • Unplug the fan motor.

    • Place the black lead on the motor's black wire.

    • Place the red lead on other fan leads one at a time.

    • Refer to charts for proper ohm readings.

Sample Ohm Readings by Model

Model Red-Black White-Black Yellow-Black Brown/Blue-Black
AOU9RLFC 300K-OL 110K-130K 70K-90K Mega Ohms-OL
AOU18RLXFW 300K-OL 45K-55K 120K-140K Mega Ohms-OL
AOU24RLXFW 300K-OL 40K-100K 120K-140K Mega Ohms-OL
AOU36RLXB 300K-OL 45K-55K 120K-140K Mega Ohms-OL
AOU15RLFF 300K-OL 110K-130K 90K-105K 75K-100K
AOU18RLFC 300K-OL 45K-55K 120K-140K Mega Ohms-OL
AOU24RLXFZ 300K-OL 40K-100K 120K-140K Mega Ohms-OL
AOU30RLX 300K-OL 45K-55K 120K-140K Mega Ohms-OL
AOU42RLX 300K-OL 40K-100K 120K-140K Mega Ohms-OL
AOU48RLXFZ 300K-OL 100K-125K 240K-265K Mega Ohms-OL
AOU9RL2 300K-OL 115K-145K 75K-100K Mega Ohms-OL
AOU36RLXFZH 300K-OL 45K-55K 120K-140K Mega Ohms-OL

 

 

See attached document for the rest of the fan motor readings.

 

Here is a video on how to perform the check.

 

DC Voltage Check for Board vs. Motor Issue

  • Use provided charts to identify correct voltage values.

  • This helps confirm whether the problem is with the control board or the fan motor itself.

Outdoor Fan Motor Error
 
Outdoor fan motor error codes by model:
 
9x Operation & 7x Timer:
 
RL2 series, RLS3 series, RLS2 series, RLB/RLXB series, RLF series, RLF1 series, LUAS1 series, LMAS series, LZBS series, LZAS series, LPAS series, RGLX series, RLE series
 
 
 
5x Operation & 6x Timer:
 
RLS series, RLXS series, CQ series, RQ series, R2 series, RL series, RML series, RMLQ series, CLX series, CLX1 series, RLX series, RLXQ series, CL1 series, CL series, RLQ series
 
 
 
Continuous flash Operation & 14 flashes Timer flash:
 
ABU18RULX, ABU24RULX & ABU36RSLX
 
 
 
9 flashes on LED A, 7 flashes on LED B, 1 flash on LED E & 1 flash on LED F:
 
AOU36RLXFZH & AOU45RLXFZ
 
 
 
2 flashes on Power Mode LED, Solid Error LED, 9 flash L1, 7 flash L2, solid L5 & solid L6 / 2 flashes on Power Mode LED, Solid Error LED, 9 flash L1, 8 flash L2, solid L5 & solid L6:
 
AOU30RLXEH
 
 
 
E973 outdoor LED:
 
AOU48RLXFZ & AOU48RLXFZ1
 
 
 
97 / 98 / 1B Wired remote: 
 
UTY-RNBYU, UTY-RNNUM, UTY-RVNUM, UTY-RSNUM, UTY-DMMUM, UTY-RSRY & UTY-RNRUZ Series, UTY-RHRY
 
 
 
Outdoor Fan Motor Error Troubleshooting Checklist
 
  1. Pull disconnect for 5 minutes & reapply, check to see if error code reappears.
  2. If error code reappears turn power back off to the disconnect and check the rotation of the fan by spinning it with your hand. Check to see if there is any kind of resistance when spinning and/or if the fan stops suddenly. There should be no resistance when turning and the fan should stop slowly not suddenly or abruptly. 
  3.  If motor spins with no problems proceed to ohm the fan motor windings with a quality ohm meter. 
  4. If the fan motor ohms bad it is a good practice to replace the Main Control board with it as defective fan motor windings can have a negative effect on the Main Control board.  