ICP VFD Settings
print icon

Variable Frequency Drives General Information

The VFD should never be used to balance air flow. A jumper is provided that allows the drive to operate at 60Hz. This Jumper should be used to place the drive at its maximum hertz and all other air flow adjustments should be done with the blower sheaves and pulleys. Failure to do so may cause erratic operation of the blower system. 

The factory is currently rolling out a sticker that will be placed on the drive to provide the proper settings for the drive. 

  

 Until the factory fully implements this procedure it is recommended that anyone connecting a key pad to modify the settings please review one of the following manual. 

 

513 06 2903 01 ICP VFD Manual 

 

Wild Leg Power Supply 

Check the power to the unit before startup. A better procedure would be to check power supply to the replacement unit before recommending a VFD unit for replacement. Wild Leg Power Supply requires a field supplied Delta-WYE transformer

This is less common power supply today but does occur in older city areas. Voltage reading look like this. 

L1 to ground 120 volts

L2 to ground 240 volts

L3 to ground 120 volts 

Note: the higher voltage on one leg with normal voltages on the other 2 legs. 

Wild Leg Power Supply 

Requires the installation of a Delta-Wye transformer to operate the VFD.

Several bulletins are available on HVAC Partners

 National Service Managers Meetings discussing VFD Topics 

 

 

 

 

 

Parameters 

Parameter

Description

Setting ACS320

Setting ACH550

9802

COMM PROT Sel

Not Selected 

Not Selected 

9902

Application Macro

(1) HVAC DEFAULT

(1) HVAC DEFAULT

9905

Motor Nominal Voltage

See Motor Table 

See Motor Table 

9906

Motor Nominal Current

See Motor Table 

See Motor Table 

9907

Motor Nominal Frequency

60 HZ

60 HZ

9908

Motor Nominal Speed 

See Motor Table 

See Motor Table 

9909

Motor Nominal Power 

See Motor Table 

See Motor Table 

1001

EXT1 Commands

(1) DI1

DI1

1003

Direction 

(1) Forward

Forward

1102

EXT1/EXT2 SEL

(0) Not Sel

EXT1

1103

REF 1 Select

(1) AI1

AI1

1104

REF 1 Minimum

0 HZ

0.0 HZ 0 RPM

1105

REF 1 Maximum

60 HZ

60.0 HZ/1500 rpm

1201

Constant Speed Select

(8) DI2 and DI3 Make Sure this is NOT INV

(8) DI2 and DI3 Make Sure this is NOT INV

1202

Constant Speed 1

40HZ 

40HZ 

1203

Constant Speed 2

60HZ

60HZ

1204

Constant Speed 3

60HZ

60HZ

1205

Constant Speed 4

Not Selected 

Not Selected 

1301

Minimum AI-1

20.00%

20.00%

1302

Maximum AI-1

100.00%

100.00%

1401

Relay Output 1

(16) FLT/ALARM

Not Selected 

1402

Relay Output 2

Not Selected 

Not Selected 

1403

Relay Output 3

Not Selected 

(16) FLT/Alarm

1501

AO1 Content

Not Selected 

Output Freq

1601

RUN Enabled

Not Selected 

Not Selected 

1604

Fault Reset Sel

(0) Keypad

Keypad

1608

Start Enable 1

(4) DI4

DI4

1611

PARAMETER View

(3) Long  View

Default (0)

2003

Maximum Current

See Motor Table 

See Motor Table 

2007

Minimum Frequency

0.0 HZ

0.0 HZ

2008

Maximum Frequency 

60HZ

60HZ

2101

Start Function

(1) Auto

(1) Auto

2102

Stop Function 

(1) Coast

(0) Ramp

2109

EM STOP Sel

(0) Not Sel

Not Selected 

2201

ACCEL/DECEL

(0) Not Sel

Not Selected 

2202

Accelerate Time

30s

30s

2203

Decelerate Time

30s

30s

2603

IR COMP Volt

0 volts

0 Volts

2606

Switching Freq

4 HZ

4 kHz

2607

Switching Freq Control

(1) ON

On

3102

Trial Time

300.0s

30.0s

3103

Delay Time

6.0s

6.0s

3104

AR Overcurrent

(1) Enabled

(0) Disabled

3105

AR Overvoltage

(1) Enabled

(1) Enabled

3106

AR Undervoltage

(1) Enabled

(1) Enabled

5101

FBA Type 

Not Selected 

Not Selected 

5201

Station ID

(1) Default

(1) Default

5202

Baud Rate

9.6 Kbits/s default

9.6 Kbits/s default

5203

Parity

(0) 8N1-8 default

(0) 8N1-8 default

5301

EFB Protocol ID

0000 hex default

0000 hex default

5302

EFB Station ID

1 Default

1 Default

5303

EFB Baud Rate

9.6 Kbits/s default

9.6 Kbits/s default

5304

EFB Parity

(0) 8 NONE 1 

(0) 8 NONE 1 

5305

EFB CTRL Profile

(0) Default

(0) Default

Please observe that under ACS320 there are only a few parameters that change those marked as See Motor Table all other parameters are the same for all Electro-Mechanical ACS320 drives. The same is true for the ACH550 Electro-Mechanical drives. These drives are also called Staged Air Volume (SAV). The RED parameters were updated by the factory and are now set in the production process. 

Consult one of the Variable Frequency manual to get the SEE MOTOR TABLE Information.  

 

513 06 2903 01 ICP VFD Manual 

See EXAMPLE Next Page. 

 

 

 

 

 

 

 

 

Parameter 1201

Parameter 1201 seems to be a parameter that is often set incorrectly in the field when field programming the drive. 

 

As you can see there are a lot of different choices. The drive should be set for:

 

If the -8 is selected then the drive will run with not call from the thermostat when you turn on the power to the unit and the drive will shut down when it receives a call from the thermostat. INV=Inverse works just the opposite as expected. 

 

Always check to ensure that INV has not been selected. 

 

 