You are using an unsupported browser. Please update your browser to the latest version on or before July 31, 2020.
close
You are viewing the article in preview mode. It is not live at the moment.
Home > Product Information > Honeywell C7835A1009 Discharge Air Temperature Sensor Instructions
Honeywell C7835A1009 Discharge Air Temperature Sensor Instructions
print icon

 

APPLICATION
The C7835A1009 Discharge Air Temperature Sensor
(DATS) is a duct-mounted temperature probe that
provides capacity control of heating and cooling
equipment. It is used only with Honeywell networked
zoning. Mounted in the supply air duct, the DATS senses
the delivered air temperature and cuts off the heating or
cooling when the delivered air temperature goes above
or below normal operating limits. The heating and cooling
limits are field-adjustable.The DATS also compares the
discharge air temperature to the room temperature and,
if out of tolerance, a heating or cooling alert is issued. In
normal operation, the heat and cool lights are off, and the
COM light blinks periodically with activity on the
Enviracom bus.
When either limit setting is reached, the heating or
cooling shuts off, and the LEDs operate according to
Table 1. The call still exists and heated or cooled air is
still being supplied to the calling zones. Once the
delivered air temperature drops ten degrees for heating,
or rises ten degrees for cooling, the heating or cooling
equipment is brought back on. The ten degree differential
provides adequate minimum time-off to avoid damaging
the equipment.
NOTE: When using 50 Hz power, cut Jumper W1.
The location of the DATS is critical; it should not be
placed in line-of-sight of the heat exchanger or cooling
coil because the DATS could activate prematurely. It
should also be located before the bypass damper, when
applicable. See Fig. 1 for dimensions.
The DATS requires only three wires. Normal 18-22
gauge thermostat wire is used.

 

IMPORTANT
Do not locate the DATS probe in a duct near the
heat exchanger or strip heat, which can cause
false temperature readings.

 

TROUBLESHOOTING Fig. 4. DATS wiring to Enviracom™ bus.
Table 1. LED Operation.
When DATS LED is... It means... It is corrected when...          
Continuously red in heating. Heating limit was exceeded. Duct air temperature falls 10°F.          
Continuously green in cooling. Cooling limit was exceeded. Duct air temperature rises 10°F.          
Flashing red. Heating system alert.a Discharge air is within 10°F of room temperature continuously in heating mode.          
Flashing green. Cooling system alert.a Discharge air is within 8°F of room temperature continuously in cooling mode.          
aHeating or cooling system alerts can be cleared by cycling power, switching modes from heat to cool or vice versa, or automatically when the equipment begins to operate correctly.
See Table 2 for resistance reading for each temperature
to determine if the DATS is reading the correct temperature. To obtain a correct resistance
measurement, remove the sensor probe P1 connector
from the circuit board. Measure resistance across the two sensor wires.
69-1463-2                                                                                           2

 

DATS Sensor Ohm Chart:

Temperature (°F) Resistance Temperature (°F) Resistance          
32 33630 117 3915          
33 32668 118 3830          
34 31737 119 3747          
35 30835 120 3666          
36 29962 121 3587          
37 29117 122 3510          
38 28298 123 3435          
39 27505 124 3362          
40 26737 125 3290          
41 25993 126 3221          
42 25272 127 3153          
43 24573 128 3086          
44 23896 129 3021          
45 23240 130 2958          
46 22604 131 2896          
47 21988 132 2836          
48 21390 133 2777          
49 20810 134 2720          
50 20248 135 2664          
51 19703 136 2609          
52 19175 137 2555          
53 18662 138 2503          
54 18165 139 2452          
55 17683 140 2402          
56 17215 141 2353          
57 16761 142 2306          
58 16320 143 2259          
59 15892 144 2214          
60 15477 145 2170          
61 15074 146 2126          
62 14683 147 2084          
63 14303 148 2043          
64 13934 149 2002          
65 13576 150 1963          
66 13229 151 1924          
67 12891 152 1886          
68 12563 153 1849          
69 12244 154 1813          
70 11935 155 1778          
71 11634 156 1744          
72 11342 157 1710          
73 11058 158 1677          
74 10782 159 1645          
75 10514 160 1613          
76 10253 161 1582          
77 10000 162 1552          
78 9754 163 1523          
79 9514 164 1494          
3                                                                                 69-1463-2
C7835A1009 DISCHARGE AIR TEMPERATURE SENSOR
 
Table 2. DATS Resistance Cross Referencea.  (Continued)
Temperature (°F) Resistance Temperature (°F) Resistance          
80 9281 165 1466          
81 9055 166 1438          
82 8835 167 1411          
83 8621 168 1385          
84 8412 169 1359          
85 8210 170 1334          
86 8013 171 1309          
87 7821 172 1285          
88 7634 173 1261          
89 7453 174 1238          
90 7276 175 1215          
91 7104 176 1193          
92 6937 177 1171          
93 6774 178 1150          
94 6615 179 1129          
95 6461 180 1108          
96 6311 181 1088          
97 6164 182 1069          
98 6022 183 1050          
99 5883 184 1031          
100 5748 185 1012          
101 5617 186 994          
102 5488 187 977          
103 5363 188 959          
104 5242 189 943          
105 5123 190 926          
106 5008 191 910          
107 4895 192 894          
108 4786 193 878          
109 4679 194 863          
110 4575 195 848          
111 4473 196 833          
112 4374 197 819          
113 4278 198 805          
114 4183 199 791          
115 4092 200 777          
116 4002          
aTo obtain a correct resistance measurement, be sure the sensor probe is disconnected from the circuit board.
For Internet access: www.trolatemp.com   or
www.honeywell.com/yourhome/zoning/zoning_home.htm
For technical support, call 1-800-TAT-Temp (1-800-828-8367). To download Zoning literature: http:hbctechlit.honeywell.com
Feedback
0 out of 0 found this helpful

scroll to top icon