Top 10 Install Oopsies
-
Wrong communication wire used – must use Fujitsu pink OR seek approval on alternative prior to installation.

-
Piping accessories installed in incorrect orientation.

-
Wrong address setting. Mixing the rotatory switches, not setting them, mismatching…

-
Power not applied to ODU 12 hours before start-up
-
Not setting (F) 21-02 Outdoor Unit "Priority Given To the Master Indoor Unit" creating complications in how mode can change

-
Incorrect connection of X1X2 and Y1Y2 on indoor units


-
Need to measure terminal resistance at various points along communication network. Failure to have correct setting of 5-4 terminal resistors when multiple refrigeration circuits are connected on Z1Z2 or requiring signal amplifier to support size of communication wiring
-
Not connecting outdoor units on communication network
-
Not setting static pressure on ducted units
-
Not setting system to sense temperature on the thermostat