Top Ten Install Problems For Fujitsu VRF
print icon

Top 10 Install Oopsies  

  1. Wrong communication wire used – must use Fujitsu pink OR seek approval on alternative prior to installation. 

Fujitsu Pink Cable

  1. Piping accessories installed in incorrect orientation. 

  1. Wrong address setting. Mixing the rotatory switches, not setting them, mismatching… 

  1. Power not applied to ODU 12 hours before start-up 

  1. Not setting (F) 21-02 Outdoor Unit "Priority Given To the Master Indoor Unit" creating complications in how mode can change 

  1. Incorrect connection of X1X2 and Y1Y2 on indoor units  

  1. Need to measure terminal resistance at various points along communication network. Failure to have correct setting of 5-4 terminal resistors when multiple refrigeration circuits are connected on Z1Z2 or requiring signal amplifier to support size of communication wiring 

  1. Not connecting outdoor units on communication network 

  1. Not setting static pressure on ducted units 

  1. Not setting system to sense temperature on the thermostat  

 

 

 