Home > HVAC Equipment Lines > Goodman Equipment > Goodman Bulletins > Goodman BGK Blower Kit Guard Issues
Goodman BGK Blower Kit Guard Issues
print icon

After the install BGK blower guard kit. We have noticed a few issues. These were put on due to the bulletin SF-090 .If you have a furnace that is giving you trouble after this kit has been put on, please submit the following information on a ticket to us so we can get the problem taken care of. We may be able to get the blower guard kit approved for removal and the drain pan kit. DPKT- 3 put on.  It's only happens on a strict case by case basis, so if you have multiple units we need to have multiple tickets written up. Thanks

 

MODEL/SERIAL OF THE EQUIPMENT​

HOME OWNER INFORMATION​

ELECTRICAL SUPPLY VOLTAGE TO THE CONTROL BOARD​

IS UNIT PROPERLY GROUNDED (Y/N)​

H-L-N FROM APPLIANCE TO BREAKER PANEL (Y/N)​

CONTROL VOLTAGE (R-C)​

GAS PRESSURE (HI AND LO IF 2 STAGE)​

IS CORRECT KIT BEING USED​

E.S.P. (EXTERNAL STATIC PRESSURE, ONLY HI FIRE)​

PICTURE OF BGK INSTALLED (ALL WIRING MUST BE VISIBLE)​

FAULT AT TIME OF SERVICE (BGK BOARD AND MAIN BOARD)