If you are needing the power requirements for Fujitsu 460V 3 phase units, please see the following...
Fujitsu VRF units will handle delta and wye configurations with no issue.
Voltage: 414 to 506 VAC
460V 3PH +/- 10% - This is typically found in the Wye configuration
480V 3PH +/- 10% - This is typically found in the Delta Configuration
Verify voltage being delivered- Make sure in the 414-506V range before flipping the disconnect