Furnace Fuse Pops When AC or Heat Pump Turns On
print icon

We have come across some jobs in the past where the furnace 3 amp fuse blows when the AC or Heat Pump is activated. Diagnosis is below.

 

Diagnosis:

 

  1. Replace Fuse
  2. Restart call or heat pump or Air Conditioner
  3. Does unit fuse pop soon after the unit starts? Or immediately?

 

  • Immediately- Verify contactor and wiring. Shorted Contactor is usually the culprit.
  • Soon after -  This is typically due to one of the high or low pressure switches in the condenser. Use jumpers to jump past the switches, test operation.

 

For replacement:

Typically these are brazed in to the units refrigeration circuit. It is easiest to get a tee for your service valve and a new pressure switch of the same rating. 