Install Tip: Best Practices for Fujitsu VRF System Communication Wiring
To ensure reliable communication and prevent common issues in Fujitsu VRF installations, follow these best practices:
✅ Use Conduit: Whenever possible, run the communication cable inside conduit to protect it from weather exposure and potential pest damage.
✅ Minimize Cable Length: Keep wire runs as short as possible to reduce the risk of signal loss and simplify troubleshooting.
✅ Avoid Bundled Loops: Do not leave excess wire coiled in loops, as this can create additional issues and complicate diagnostics.
✅ Follow a Clear Wiring Path:
-
Daisy Chain Wiring: When connecting units, daisy chain from the outdoor unit to its connected indoor units using X1/X2 terminals.
-
Outdoor Unit Connections: Daisy chain between outdoor units using Z1/Z2 terminals for streamlined communication paths.
By following these tips, you can reduce the likelihood of communication errors and simplify future maintenance.