Fujitsu VRF Communication Wire Wiring (Fujitsu Pink Cable) Install Tip
print icon

Install Tip: Best Practices for Fujitsu VRF System Communication Wiring

To ensure reliable communication and prevent common issues in Fujitsu VRF installations, follow these best practices:

 

Use Conduit: Whenever possible, run the communication cable inside conduit to protect it from weather exposure and potential pest damage.

 

Minimize Cable Length: Keep wire runs as short as possible to reduce the risk of signal loss and simplify troubleshooting.

 

Avoid Bundled Loops: Do not leave excess wire coiled in loops, as this can create additional issues and complicate diagnostics.

 

Follow a Clear Wiring Path:

  • Daisy Chain Wiring: When connecting units, daisy chain from the outdoor unit to its connected indoor units using X1/X2 terminals.

  • Outdoor Unit Connections: Daisy chain between outdoor units using Z1/Z2 terminals for streamlined communication paths.

 

By following these tips, you can reduce the likelihood of communication errors and simplify future maintenance.

    