Fault Codes Table for Fujitsu Minisplit - Errors Display On Lights Of The Indoor Unit (Operation, Timer, Economy) Or Wired Remote Controller - E: "Error Code" 

Error Code Unit Type Error Description Operation LED Timer LED Economy LED Troubleshooting Steps
E: 11 Outdoor Serial communication error (Serial reverse transfer) 1 Flash 1 Flash Continuous Check wiring between indoor and outdoor units; inspect for loose connections. Potential need to replace components
E: 11 Indoor Serial communication error (Serial forward transfer) 1 Flash 1 Flash Continuous Check wiring between indoor and outdoor units; inspect for loose connections. Potential Need to replace components
E: 12 Indoor Wired remote controller communication error 1 Flash 2 Flashes Continuous Verify remote controller wiring; ensure connections are secure. Is remote Compatible?
E: 15 Indoor Automatic air flow adjustment error 1 Flash 5 Flashes Continuous Clean air filters; check fan motor operation. Try again. Otherwise Measure static with manometer and set manually.
E: 18 Indoor External communication error 1 Flash 8 Flashes Continuous Verify communication cable connections; reset the system.
E: 22 Indoor Indoor unit capacity error 2 Flashes 2 Flashes Continuous Confirm correct indoor unit model; check PCB settings. Verify power to all indoor units
E: 23 Outdoor Combination error 2 Flashes 3 Flashes Continuous Confirm compatible unit combinations; inspect wiring connections.
E: 26 Indoor Address setting error in wired remote controller 2 Flashes 6 Flashes Continuous Verify address settings; reset controller.
E: 29 Indoor Connected unit number error 2 Flashes 9 Flashes Continuous Ensure correct unit addressing; confirm total connected units.
E: 32 Indoor Indoor unit main PCB error 3 Flashes 2 Flashes Continuous Inspect PCB for damage; replace if needed.
E: 33 Indoor Indoor unit motor electricity consumption detection 3 Flashes 3 Flashes Continuous Check motor wiring; replace motor if faulty.
E: 35 Indoor MANUAL AUTO button error 3 Flashes 5 Flashes Continuous Inspect control board; replace button if defective.
E: 39 Indoor Indoor unit power supply error for fan motor 3 Flashes 9 Flashes Continuous Check power supply; ensure correct voltage.
E: 3A Indoor Indoor unit communication circuit error (wired remote) 3 Flashes 10 Flashes Continuous Inspect wiring for damage; verify wiring is correct. reset the system.
E: 41 Indoor Room temperature sensor error 4 Flashes 1 Flash Continuous Replace room temperature sensor.
E: 42 Indoor Indoor unit heat exchanger sensor error 4 Flashes 2 Flashes Continuous Replace heat exchanger sensor.
E: 45 Indoor Refrigerant leakage sensor error 4 Flashes 5 Flashes Continuous Inspect for refrigerant leaks; replace sensor if necessary.
E: 51 Indoor Indoor unit fan motor error 5 Flashes 1 Flash Continuous Inspect fan motor wiring; replace motor if defective.
E: 53 Indoor Drain pump error 5 Flashes 3 Flashes Continuous Clear drain line; inspect pump operation.
E: 62 Outdoor Outdoor unit model information error 6 Flashes 2 Flashes Continuous Verify outdoor unit model settings; check PCB.
E: 63 Outdoor Inverter error 6 Flashes 3 Flashes Continuous Inspect inverter wiring; replace inverter if needed.
E: 64 Outdoor Active filter voltage error 6 Flashes 4 Flashes Continuous Check power supply voltage; inspect wiring.
E: 65 Outdoor IPM error 6 Flashes 5 Flashes Continuous Inspect IPM module; replace if faulty.
E: 71 Outdoor Discharge thermistor error 7 Flashes 1 Flash Continuous Replace discharge thermistor. Verify EEV, Verify Charge
E: 72 Outdoor Compressor thermistor error 7 Flashes 2 Flashes Continuous Replace compressor thermistor. Verify EEV. Verify Charge
E: 73 Outdoor Outdoor unit heat exchanger thermistor error 7 Flashes 3 Flashes Continuous Replace heat exchanger thermistor. Check for Debris on coil
E: 74 Outdoor Outdoor temperature thermistor error 7 Flashes 4 Flashes Continuous Replace outdoor temperature thermistor.
E: 76 Outdoor 2-way valve/3-way valve thermistor error 7 Flashes 6 Flashes Continuous Inspect thermistor wiring; ohm out and replace thermistor if needed.
E: 77 Outdoor Heat sink thermistor error 7 Flashes 7 Flashes Continuous Replace heat sink thermistor.
E: 84 Outdoor Current sensor error 8 Flashes 4 Flashes Continuous Inspect current sensor wiring; replace sensor if necessary.
E: 86 Outdoor High pressure switch error 8 Flashes 6 Flashes Continuous Inspect refrigerant pressure; replace switch if needed.
E: 94 Outdoor Over current error 9 Flashes 4 Flashes Continuous Inspect wiring and power supply for overload issues. Verify Compressor and Fan Motor
E: 95 Outdoor Compressor motor control error 9 Flashes 5 Flashes Continuous Inspect Compressor wiring; replace control module if needed. Verify Linesets
E: 97 Outdoor Outdoor unit fan motor error 9 Flashes 7 Flashes Continuous Inspect fan motor wiring; replace motor if defective. Does Fan Spin Freely?
E: 99 Outdoor 4-way valve error 9 Flashes 9 Flashes Continuous Inspect valve wiring; replace 4-way valve if faulty.
E: A1 Outdoor Discharge temperature error 10 Flashes 1 Flash Continuous Inspect discharge temperature sensor; replace if defective. Verify Charge

 

 

Error Contents Operation Lamp (Green) Timer Lamp (Orange) Economy Lamp (Green) Wired Remote Display
Communication & Addressing        
Serial Communication Error 1 flash 1 flash Continuous 11
Wired Remote Controller Comm. Error 1 flash 2 flashes Continuous 12
Unit Number or Refrigerant Circuit Address Error 2 flashes 1 flash Continuous 21
Address Setting Error (Dual Address Exists) 2 flashes 6 flashes Continuous 26
Indoor Unit Components        
Indoor Unit Capacity Error 2 flashes 2 flashes Continuous 22
Connecting Number of Indoor Unit Error 2 flashes 4 flashes Continuous 24
Indoor Unit Model Info Error (EEPROM Access) 3 flashes 2 flashes Continuous 32
Manual Auto Switch Error 3 flashes 5 flashes Continuous 35
Indoor Room Thermistor Error 4 flashes 1 flash Continuous 41
Indoor Heat Exchanger Thermistor Error 4 flashes 2 flashes Continuous 42
Indoor Unit Fan Motor Error 5 flashes 1 flash Continuous 51
Drain Pump Error 5 flashes 3 flashes Continuous 53
Damper Error 5 flashes 7 flashes Continuous 57
Outdoor Unit & Inverter        
Outdoor Unit Model Info Error (EEPROM) 6 flashes 2 flashes Continuous 62
Inverter Error 6 flashes 3 flashes Continuous 63
Active Filter Error 6 flashes 4 flashes Continuous 64
IPM Error 6 flashes 5 flashes Continuous 65
CT Error 8 flashes 4 flashes Continuous 84
Over Current Error 9 flashes 4 flashes Continuous 94
Compressor Control Error 9 flashes 5 flashes Continuous 95
Outdoor Unit Fan Motor Error 9 flashes 7 flashes Continuous 97
Sensors & Valves        
Discharge Thermistor Error 7 flashes 1 flash Continuous 71
Compressor Thermistor Error 7 flashes 2 flashes Continuous 72
Heat Exchanger Thermistor Error (OUT) 7 flashes 3 flashes Continuous 73
Outdoor Thermistor Error 7 flashes 4 flashes Continuous 74
2-Way Valve Thermistor Error 7 flashes 6 flashes Continuous 76
3-Way Valve Thermistor Error 7 flashes 6 flashes Continuous 76
Discharge Pressure Sensor Error 8 flashes 6 flashes Continuous 86
4-Way Valve Error 9 flashes 9 flashes Continuous 99
Coil (Expansion Valve) Error 9 flashes 10 flashes Continuous 9A
Performance & Temperature        
Discharge Temp. Error 10 flashes 1 flash Continuous A1
Compressor Temp. Error 10 flashes 3 flashes Continuous A3
Poor Refrigerant Circulation 10 flashes 8 flashes Continuous A8
Feedback