Fujitsu Troubleshooting – No Error Codes Displayed
When working on Fujitsu multi-zone systems that do not show error codes, follow the logical progression below to diagnose based on symptoms and test results.
1. Initial System Behavior
Condition:
System acted like it was low on refrigerant.
Next Steps:
-
Add refrigerant and observe pressure behavior.
If pressures continue to drop:
-
Probable Cause: Refrigerant still too low or system restriction.
2. EEV and Electrical Checks
Condition:
Ohm readings on each EEV are within spec.
Interpretation:
-
Probable Cause: EEVs are electrically sound, but mechanical failure or blockage is still possible.
Compressor ohm readings and voltage supply are also normal.
-
Probable Cause: Compressor is electrically OK and receiving voltage. Suspect internal failure if not pumping.
3. Operation Tests in Heating Mode
Condition:
-
Compressor sounds normal.
-
Reversing valve activates.
-
Pressures do not respond.
Probable Causes:
-
Low charge or compressor is not moving refrigerant.
4. Cooling Mode Test
Condition:
-
System pulled into a vacuum (~0 psi) after 6 minutes of cooling.
-
No error codes.
-
Pressures around 80–100 psi.
-
System shuts off after ~10 minutes.
Probable Causes:
-
Severe restriction, likely at the EEV.
-
Pressures should typically be around 110–130 psi.
-
System may be shutting down on high/low pressure switch or current sensing (amp draw).
5. Head Unit Temperature Output
Condition:
-
South head: 126°F air
-
North head: 68°F air
-
After 30 mins, both heads: 68°F
Probable Causes:
-
Restriction in North head refrigerant circuit.
-
Outdoor unit may have shut off due to internal protection (pressure or amp draw).
6. System History and Contaminant Risk
Condition:
-
Previous tech brazed a leak.
-
Recommendation to replace compressor or outdoor unit.
Probable Cause:
-
Brazing without proper evacuation or filtration can introduce contaminants.
-
Leads to clogs, restrictions, and overall erratic performance.
7. Final Observation
Condition:
After power reset, South head continues to blow warm air, North still ineffective.
Probable Cause:
-
North unit likely has a restriction.
-
System is partially operational but inefficient.
Bot Logic Summary (for implementation)
A bot can ask:
-
“Is the system displaying error codes?”
-
“What are the pressures in cooling and heating modes?”
-
“Are individual head units behaving differently?”
-
“Have you checked EEVs and compressor electrically?”
-
“Have contaminants ever been introduced (e.g., leak repairs)?”
From the answers, it can follow conditional logic like:

