This details the the communication checks for the R32 Units. This is not for R410a models. Be sure to verify what you have before testing.
Communication Errors – Key Checks (R32 Units)
If you encounter a communication error on an R32 unit, follow these key steps:
1. Verify Wired Wi-Fi Module & Condensate Pumps
-
If a wired Wi-Fi module is installed but Wi-Fi is unavailable, it can trigger a communication fault.
-
Check any condensate pumps wired into the system—ensure none have opened a communication lead.
2. Check 3-Pole Disconnects
-
Ensure all connections are tight and free of corrosion.
-
Test across the disconnect for voltage drop—there should be none.
-
If needed, reset the disconnect before proceeding.
3. Inspect Wiring & Grounding
-
No wire nuts should ever be used on communication lines.
-
Confirm correct wiring practices and proper equipment grounding.
4. Test for Communication Signal (R32-Specific Method)
-
Step 1: Remove wire #3 at the indoor unit terminal block.
-
Step 2: Test from the empty #3 screw to the ground screw.
-
✅ Expected Reading: A steady voltage above 100 VDC.
(This confirms a good signal is coming from the outdoor unit.)
-
-
Step 3: Test from the removed wire #3 to the ground screw.
-
✅ Expected Reading: A fluctuating voltage of 60 VDC or greater.
(This confirms communication signal activity returning from the indoor unit.)
-
🔄 Note: These readings are the opposite of what you’d expect on R410A systems.
-
If expected voltages are not present, investigate:
-
Damaged or miswired cables
-
Failed control board(s)
-
Open or shorted components
-
5. Verify Power to Indoor & Outdoor Units
-
Ensure 230V is present at both indoor and outdoor units.
-
If power is missing at the indoor unit, check for:
-
Blown fuses
-
Faulty wiring
-
-
Outdoor unit fuses often protect the indoor board, so check both ends.
6. Check for Faulty Control Board & Components
Before replacing any control board, always test:
-
EEV(s)
-
Compressor
-
Fan Motor(s)
⚠️ If one of these is faulty, replacing the board alone won’t solve the issue—it will likely fail again.
7. Replace the Active Filter Module (ACTPM)
When replacing a control board, also replace the Active Filter Module. The ACTPM protects against voltage spikes and electrical noise.
🆕 Note: On R32 units, the Active Filter Module (ACTPM) is built into the main board.
You no longer need to test or replace this as a separate component.
7. Final System Testing
After confirming all components and wiring, proceed with normal system testing and commissioning.
Component Failure Errors – Best Practices
For any error codes related to component failure:
-
Double-check all major components:
-
EEV
-
Fan Motor
-
Compressor
-
🔧 Proactive Maintenance Tip
Encourage techs to test these components during regular PM calls. Early detection reduces callbacks and prevents unnecessary board replacements.

