You are using an unsupported browser. Please update your browser to the latest version on or before July 31, 2020.
close
You are viewing the article in preview mode. It is not live at the moment.
Fujitsu Communication Error 1.1 Checks R32 Units
print icon

This details the the communication checks for the R32 Units. This is not for R410a models. Be sure to verify what you have before testing.

 

Communication Errors – Key Checks (R32 Units)

If you encounter a communication error on an R32 unit, follow these key steps:

1. Verify Wired Wi-Fi Module & Condensate Pumps

  • If a wired Wi-Fi module is installed but Wi-Fi is unavailable, it can trigger a communication fault.

  • Check any condensate pumps wired into the system—ensure none have opened a communication lead.

2. Check 3-Pole Disconnects

  • Ensure all connections are tight and free of corrosion.

  • Test across the disconnect for voltage drop—there should be none.

  • If needed, reset the disconnect before proceeding.

3. Inspect Wiring & Grounding

  • No wire nuts should ever be used on communication lines.

  • Confirm correct wiring practices and proper equipment grounding.

4. Test for Communication Signal (R32-Specific Method)

  • Step 1: Remove wire #3 at the indoor unit terminal block.

  • Step 2: Test from the empty #3 screw to the ground screw.

    • Expected Reading: A steady voltage above 100 VDC.
      (This confirms a good signal is coming from the outdoor unit.)

  • Step 3: Test from the removed wire #3 to the ground screw.

    • Expected Reading: A fluctuating voltage of 60 VDC or greater.
      (This confirms communication signal activity returning from the indoor unit.)

🔄 Note: These readings are the opposite of what you’d expect on R410A systems.

  • If expected voltages are not present, investigate:

    • Damaged or miswired cables

    • Failed control board(s)

    • Open or shorted components

5. Verify Power to Indoor & Outdoor Units

  • Ensure 230V is present at both indoor and outdoor units.

  • If power is missing at the indoor unit, check for:

    • Blown fuses

    • Faulty wiring

  • Outdoor unit fuses often protect the indoor board, so check both ends.

6. Check for Faulty Control Board & Components

Before replacing any control board, always test:

  • EEV(s)

  • Compressor

  • Fan Motor(s)

⚠️ If one of these is faulty, replacing the board alone won’t solve the issue—it will likely fail again.

7. Replace the Active Filter Module (ACTPM)

When replacing a control board, also replace the Active Filter Module. The ACTPM protects against voltage spikes and electrical noise.

🆕 Note: On R32 units, the Active Filter Module (ACTPM) is built into the main board.
You no longer need to test or replace this as a separate component.

7. Final System Testing

After confirming all components and wiring, proceed with normal system testing and commissioning.


Component Failure Errors – Best Practices

For any error codes related to component failure:

  • Double-check all major components:

    • EEV

    • Fan Motor

    • Compressor

🔧 Proactive Maintenance Tip

Encourage techs to test these components during regular PM calls. Early detection reduces callbacks and prevents unnecessary board replacements.

Feedback
0 out of 0 found this helpful

scroll to top icon