Pre-Setup
- Dip Switch: Set SW101 #3 to ON (or OFF if no heater kit).
- Battery Backup: Turn dip switch on the back of the control to ON.
Function Settings
-
Enter Function Mode: Menu Key > Maintenance > Function Setting. Password: 0000.
-
Temperature Sensing:
- Function 42: Set value 01 (indoor unit + wired controller).
- Function 48: Set value 01 (wired controller only).
- Enable RC Sensor to "Use".
-
Fan Control: Function 49: Set value 02 (fan on/off by wired controller).
Auxiliary Strip Heat Control
-
Outdoor Temperature Control:
- Function 61: Set value 03 or 05.
- Function 66: Set outdoor temp for strip heat only.
- Function 67: Set outdoor temp for heat pump only.
-
Rapid Set Back Recovery: Function 62: Refer to Table 62.
-
Cold Climate Strip Heat Only: Function 66: Refer to Table 66.
-
Strip Heat Lock Out: Function 67: Refer to Table 67.
Additional Settings
-
Performance Override: Function 71: Set values 00 – 99.
-
Emergency Heat Control:
- Function 72: Set value 01 (fault code).
- Function 73: Set value 01 (wired controller).
-
Defrost Comfort Setting:
- Function 75: Set value 01 (strip heater during defrost).
- Function 93: Refer to Table 93 (adjust CFM).
Final Steps
- Return to the home screen and cycle power at the outdoor unit to save settings.